Programming
ABB Control - AC 31
Page 5-39
1SBC 260400 R1001-b
06.99
5.7.3. TP: monostable (constant)
This block enables the activation of an output during a fixed time as from the moment when a
rising edge appears on the input. A new rising edge will not be taken into account if it appears
on the input before the timer time has been completed.
TP
IN
PT
Q
ET
%I62.00
%KD001.00
%O62.00
%MD000.00
Q
PT
IN
PT
5.7.4. TIME_W:
The function TIME_W can be used to display elapse time on the display extension XTC 08
5.7.5. W_TIME:
The function W_TIME is needed when the time value has to be modified during program (i.e.
Control panel, supervisor, set point validation…)
TIME_W
TIME
H
MN
SEC
MS
%OW63.00
%OW63.01
%OW63.02
%OW63.03
%MD000.00
W_TIME
H
MN
SEC
MS
TIME
%OW63.00
%OW63.01
%OW63.02
%OW63.03
%MD000.00
TON
IN
PT
Q
ET
%MD000.00
%I62.00
%O62.00
%MD000.01
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...