Diagnosis
ABB Control - AC 31
Page 8-11
1SBC 260400 R1001-b
06.99
4.3.4. Class 4 error descriptions
Class 4 error descriptions
Error code in
MW255.08
Dec Hex
Info 1 in
MW 255.09
Info 2 in
MW 255.10
Info 3 in
MW 255.11
Internal unit error
1
D
01
H
Unit type
Address
Channel number
Cut wire (detection of open circuit)*
2
D
02
H
Unit type
Address
Channel number
Analog output level error
3
D
03
H
Unit type
Address
Channel number
Overload
4
D
04
H
Unit type
Address
Channel number
Defective 10V output
5
D
05
H
Unit type
Address
Channel number
Overload and cut wire*
6
D
06
H
Unit type
Address
Channel number
Short circuit
8
D
08
H
Unit type
Address
Channel number
Short-c cut wire*
10
D
0A
H
Unit type
Address
Channel number
Ov short-circuit
12
D
0C
H
Unit type
Address
Channel number
Short-c ov cut wire*
14
D
0E
H
Unit type
Address
Channel number
The end of the program is not
detected by the system during
startup.
129
D
81
H
-
-
-
A program syntax error is detected
by the system during startup
131
D
83
H
Program address
-
-
Too many historical values are
detected by the system during
startup (max. 256)
132
D
84
H
-
-
-
The cycle time is missing and
detected by the system during
startup
133
D
85
H
-
-
-
A missing label for a conditional
step is detected by the system
during startup.
135
D
87
H
Program address
-
-
The program is not launched due to
the number of units initialized on the
CS 31 bus being inferior to the
number specified during the
configuration
138
D
8A
H
Number of units
chosen during
configuration
Number of actual
units on the CS31
bus
-
The program is too large for the
memory size
140
D
8C
H
-
-
-
The system detects a missing end
of sub-program or missing program
during startup
142
D
8E
H
-
-
-
The system detects a missing
program interrupt or an interrupt
validation.
143
D
8F
H
-
-
-
The system detects too many sub-
programs (max. 12) during startup.
144
D
90
H
-
-
-
The system detects too many
historical values in the sub-
programs during startup.
(max. 128 = Sum of nb of calls x nb
of historical values in the sub-
programs)
145
D
91
H
-
-
-
The system does not detect a sub-
program, corresponding to a call,
during startup
146
D
92
H
-
-
-
* error detected if previously configured through programming the CS31CO block
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...