Programming
ABB Control - AC 31
Page 5-35
1SBC 260400 R1001-b
06.99
5.3. NAND operation
The output has a 0 status if all the inputs have a 1 status.
%O62.00
%I62.01
%I62.00
%I62.00
%I62.01
&
%O62.00
A NAND diagram has the same function as an OR diagram with the inputs inverted.
%O62.00
%I62.01
%I62.00
%I62.00
%I62.01
/
%O62.00
5.4. Operation OR
The status of an OR diagram output is 1, if at least one of the inputs has a status of 1.
The figure to the left represents a ladder diagram OR operation with three inputs. The number
of contacts, which may be placed in parallel, is unlimited.
The diagram to the right represents the same function with a function block. The number of
inputs for an OR function block is limited to a maximum of 128.
%O62.00
%I62.01
%I62.00
%I62.00
%I62.01
/
%I62.02
%I62.02
%O62.00