![ABB AC 31 Technical Manual Download Page 54](http://html.mh-extra.com/html/abb/ac-31/ac-31_technical-manual_176054.webp)
Technical specifications
ABB Control - AC 31
Page 3-11
1SBC 260400 R1001-b
06.99
40 series
50 series
07 CR 41
24 V d.c.
07 CT 41
24 V d.c.
07 CR 41
120/230 V a.c.
07 KR 51
24 V d.c.
07 KT 51
24 V d.c.
07 KR 51
120/230 V a.c.
Incorporated outputs
- Number of outputs
6 relays
6 transistors
6 relays
6 relays
6 transistors
6 relays
- Isolation of the inputs / electronic
1500 Vrms
1 min
1500 V a.c.
1500 Vrms
1 min
1500 Vrms
1 min
1500 V a.c.
1500 Vrms
1 min
- Total charging current
under voltage:
direct 24 V d.c.
resistive load / inrush current
L / R = 20 ms
L / R = 30 ms
L / R = 40 ms
L / R = 60 ms
alternate 24 to 230 V a.c.
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
1 A for
O62.00 and
O62.01 and
0.5 A for
other outputs
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
1 A for
O62.00 and
O62.01 and
0.5 A for
other outputs
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
- Total charging current
6 x 2 A
4 x 0.5 A
+ 2 x 1 A
6 x 2 A
6 x 2 A
4 x 0.5 A
+ 2 x 1 A
6 x 2 A
- Output leakage current
-
< 200
µ
A
-
-
< 200
µ
A
-
- Output waste voltage
-
0.5 V to
500 mA max.
-
-
0.5 V to
500 mA max.
-
- Minimum cut-off values
10 mA under
12 V d.c.
12 V
10 mA under
12 V d.c.
10 mA under
12 V d.c.
12V
10 mA under
12 V d.c.
- Breaking capacity under 120 V a.c.
(contact rating code B300) (UL)
2 A
2 A
2 A
2 A
- Breaking capacity under 250 V a.c.
(contact rating code B300) (UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
- Number of common
2 (2+4)
2 (2+4)
2 (2+4)
2 (2+4)
- Switching frequency:
for resistive loads
for inductive loads
for lamps
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
- Number of switches:
for AC-1
for AC-15
1 million
100 000
-
-
1 million
100 000
1 million
100 000
-
-
1 million
100 000
- Short circuit and overload
protection
envisage
externally
yes:
thermic
envisage
externally
envisage
externally
yes:
thermic
envisage
externally
- Surge voltage protection
envisage
externally
yes
envisage
externally
envisage
externally
yes
envisage
externally
- Outputs diagnosis
no
overload and
short circuit
no
no
overload and
short circuit
no
- Cable length:
unshielded
shielded
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...