Technical specifications
Page 3-8
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
3.2. Technical specification
40 series
50 series
07 CR 41
24 V d.c.
07 CT 41
24 V d.c.
07 CR 41
120/230 V a.c.
07 KR 51
24 V d.c.
07 KT 51
24 V d.c.
07 KR 51
120/230 V a.c.
Number of I/O
- Incorporated binary inputs
8
8
- Incorporated binary outputs
6
6
- Analog potentiometers
2
2
- Maximum number of extension
units per central unit
6
6
- Maximum number of remote units
on the CS 31 bus
-
31
- Max. number of binary inputs
104
1096
- Max. number of binary outputs
54
1046
- Max. number of analog inputs
48
496
- Max. number of analog outputs
12
136
Interfaces
- CS 31 interface
no
yes
- Interface for: Programming
MODBUS
®
or ASCII
1 RS 232
1 RS 232 / RS 485
Memory
- User program memory size:
without ONLINE
with ONLINE
16 000 words (typically: 8 kInstructions)
8 000 words (typically: 4 kInstructions)
16 000 words (typically: 8 kInstructions)
8 000 words (typically: 4 kInstructions)
- User program memory
and the constants
Flash Eprom
Flash Eprom
- Data memory
SRAM
SRAM
- Data backup:
Backup autonomy
Charge time under power
no
-
-
yes with battery
40 days at 25°C
100% in 12 h
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...