Technical specifications
Page 3-18
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
5.2. Binary extensions specifications
The binary extension units are powered at 5 V by the central unit or extensible remote unit to
which they are connected.
Warning: the extensions must not be connected or disconnected under power supply.
XI 16 E1
XO 08 R1
XC 08 L1
XK 08 F1
XO 16 N1
Weight
220 g
220 g
220 g
220 g
220 g
Incorporated binary inputs
- Number of inputs
16
-
8 configurable
4
-
- Isolation of the inputs/electronic
1500 V a.c.
-
1500 V a.c.
1500 V a.c.
-
- Types of inputs
PNP
-
PNP
PNP
-
- Input voltage:
Nominal value
Signal at 0 (IEC 1131-2)
Signal at 1 (IEC 1131-2)
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
-
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
-
- Input current at 24 V d.c.
4 mA
-
4 mA
7 mA
-
- Filtering time of an input
5 ms
-
5 ms
5 ms
-
- Cable length:
unshielded
shielded
300 m
500 m
-
-
300 m
500 m
300 m
500 m
-
-
Incorporated outputs
- Number of outputs
-
8 relays
8 transistors
4 relays
16 transistors
- Isolation of the outputs/electronic
-
1500 Vrms
1 min
1500 V a.c.
1 min
1500 Vrms
1 min
1500 V a.c.
1 min
- Total charging current, under voltage:
direct 24 V d.c.
resistive load / inrush current
L / R = 20 ms
L / R = 30 ms
L / R = 40 ms
L / R = 60 ms
alternate 24 to 230 V a.c.
-
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
0.5 A
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
0.5 A
-
- Total charging current
-
8 x 2 A
8 x 0.5 A
4 x 2 A
16 x 0.5 A
- Output leakage current
-
< 200
µ
A
< 200
µ
A
- Output waste voltage
-
0.5 V à 500 mA
max.
0.5 V à 500 mA
max.
- Minimum cut-off value
-
10 mA at
12 V d.c.
12 V
10 mA at
12 V d.c.
12 V
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...