4.2. Technical specifications of the extensible remote units
ICMK 14 F1
ICMK 14 F1
ICMK 14 N1
24 V d.c.
120 / 230 V a.c.
24 V d.c.
- Weight
400 g
800 g
400 g
Power supply
- Mains voltage:
Nominal value
Admissible range
24 V d.c.
19.2 to 30 V
120 or
230 V a.c.
97.75 to
126.5 V or
195.5 to 253 V
24 V d.c.
19.2 to 30 V
- Consumption:
Unit alone (typical)
Maximum configuration (typical)
80 mA
400 mA
30 mA
100 mA
80 mA
400 mA
- Polarity reversal protection
yes
-
yes
- 24 V d.c. isolated power for
the inputs:
Range of voltage value
Max. Output current
Short circuit protection
no
-
-
-
yes
19.2 to 30 V
400 mA
yes
no
-
-
-
- Dissipation
5 W
10 W
6 W
Incorporated binary inputs
- Number of inputs
8
8
8
- Isolation of the inputs / electronic
1500 V a.c.
1500 V a.c.
1500 V a.c.
- Input types
PNP and NPN
PNP and NPN
PNP and NPN
- Input voltage:
Nominal value
Signal at 0 (IEC 1131-2)
Signal at 1 (IEC 1131-2)
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
- Input current at 24 V d.c.:
Inputs Ixx.02 to Ixx.07
Inputs Ixx.00 and Ixx.01
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
- Minimum filtering time
5 ms
5 ms
5 ms
- Cable length:
unshielded
shielded
300 m
500 m
300 m
500 m
300 m
500 m
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...