Programming
Page 5-44
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
5.10.2. Processing an analog input
The following example shows how to process the measurement of a distance sensor.
Measured
physical value
V10/-10V
Power +20/-20mA
Power 4-20mA
Value read in the
central unit
100 m
10
20
20
32760
y
m
x
0 m
0
0
4
0
-10
-20
-32760
The value read in the central unit should be scaled in order to be expressed in meters so that
the information may be sent, for example, to a display. In this case the measured value
y
is
such that:
y = (100 * x) / 32760
*:
Z1*
Z2:
Z3
A1
%IW63.00
VAL_32760
VAL_100
METERS
It is not necessary to scale values to carry out comparison tests (equal, greater, lesser...). The
compared values can be those read in the central unit.