Diagnosis
Page 8-12
ABB Control - AC 31
1SBC 260400 R1001-b
06.99
4.4. Programming examples
4.4.1. Example of a reaction / command following a specific error
The following example enables commanding an alarm following an overload or short circuit on
the number 5 output of a ICMK 14 N1 remote unit with address 3 on the CS 31 bus. Another
output is also activated at the same time as the alarm in order to, for example, issue a cut the
actuators power command.
This is a class 4 type error and uses the following variables:
-
M 255.14
: class 4 error presence bit
-
MW 255.08
: the error code
-
MW 255.09
: the unit type
-
MW 255.10
: the unit address
-
MW 255.11
: the defective channel number
&
%M255.14
=?
Z1=?
Z2
Q
%MW255.08
=?
Z1=?
Z2
Q
=?
Z1=?
Z2
Q
=?
Z1=?
Z2
Q
%MW255.09
%MW255.10
%MW255.11
CODE_12
TYPE_20
ADD_3
CHANNEL_5
ALARM
SHUT_DOWN
Summary of Contents for AC 31
Page 1: ...Technical Manual Advant Controller 31 40 50 Series 1SBC 260400 R 1001 b ...
Page 7: ......
Page 43: ......
Page 45: ...Technical specifications Page 3 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 83: ......
Page 85: ...Installation Page 4 2 ABB Control AC 31 1SBC 260400 R1001 b 06 99 ...
Page 109: ......
Page 130: ...Programming ABB Control AC 31 Page 5 21 1SBC 260400 R1001 b 06 99 ...
Page 182: ...Communication ABB Control AC 31 Page 7 11 1SBC 260400 R1001 b 06 99 ...
Page 189: ......
Page 203: ......
Page 217: ......
Page 218: ...AC 31 technical documentation ABB Control AC 31 Index Page 1 1SBC 260400 R1001 b 06 99 Index ...