INSTALLER/DEALER SETTINGS
* Additional options available only
through the Dealer Code.
FIND IT
INSTALLER/DEALER
SETTINGS
Swipe down for
access
INSTALLATION
SETTINGS
ADVANCED SETTINGS
ENTER CODE (1111, 2222)
Setting
Default
Description
Account Number
blank
Security provider account number (up to 10 characters)
Power Management
Enabled
An energy-saving function when running on battery power only
SIA Power Restoration
Disabled
Turn on or o
ff
sensor hold for 60 seconds during power restore
Loss of Supervisory Signals for
Emergency Sensors
4
Select the length in hours (4, 12, 24) before reporting a loss of supervision
on life safety devices.
NOTE:
For UL/cUL Resi Fire and UL Commercial Burg (UL1610) the wireless
supervision window for Emergency sensors (Smoke, Heat & CO Detectors)
shall be set to 4h
Loss of Supervisory Signals for
PowerG Emergency Sensors
4
Select the length of time (20, 30 min, 1, 2, 4, 12, 18 hours) before reporting a
loss of supervision on PowerG life safety devices.
NOTE:
For UL/cUL Resi Fire and UL Commercial Burg (UL1610) the wireless
supervision window for Emergency sensors (Smoke, Heat & CO Detectors)
shall be set to 4h
Loss of Supervisory Signals for
Z-Wave
4
Select the length in hours
(4, 24)
before reporting a loss of supervision on Z-
Wave Sirens.
Installer/Dealer Settings
Change panel settings like supervisory times, power and cell loss timeout and SIA
settings.
PROGRAMMING
Summary of Contents for Qolsys IQ Panel 2
Page 8: ...INSTALLING THE PANEL...
Page 13: ...USER INTERFACE...
Page 17: ...PROGRAMMING...
Page 52: ...SECURITY SENSORS...
Page 84: ...WI FI DEVICES...
Page 91: ...Z WAVE DEVICES...
Page 102: ...BLUETOOTH DEVICES...
Page 110: ...SYSTEM TESTS...
Page 135: ...CUSTOMIZATION...
Page 148: ...MAINTENANCE...
Page 154: ...TROUBLESHOOTING...
Page 164: ...LEGAL...
Page 172: ...SPECIFICATIONS...