13.3.3 pH Delay On Time
The delay on time sets the amount of time the controller
waits to dose the pool again.
On the CHEMLINK pH setup screen, select the DELAY
OT time. Use the UP and DOWN arrows to change this
time. Click SAVE when finished.
ChemLink
Home
Menu OneTouch
Help
Back
Status
Thu June 23, 2011 3:03 PM
ChemLink 1 pH
Status
Feeder
LIQUID
Feed TM
15 SEC
Delay OT
45 Min
Set Point
7.0
High Alert
8.0
Adjust
Low Alert
8.0
Page
Down
Page
Up
Save
Orp
pH
Type
ERO LP/MBV/ERO HP
Liquid
Default
Do not use
30 Sec
Range
.05 Sec to
CONT
13.3.4 pH Setpoint
This setting specifies the level of sanitizer to be
maintained.
On the CHEMLINK pH setup screen, select the SET
POINT values. Use the UP and DOWN arrows to adjust
the SET POINT values.
ChemLink
Home
Menu OneTouch
Help
Back
Status
Thu June 23, 2011 3:03 PM
ChemLink 1 pH
Status
Feeder
LIQUID
Feed TM
15 SEC
Delay OT
45 Min
Set Point
7.0
High Alert
8.0
Adjust
Low Alert
8.0
Page
Down
Page
Up
Save
Orp
pH
Default
7.5
Range
7.0 to 8.2
13.3.5 pH Alarm - High Alert
The high alert alarm sets an alarm to deactivate the
controller in the event of a pH reading that is out of
high range. This could be an indication of a mechanical
malfunction in the feeding system.
On the CHEMLINK pH setup screen, select the HI
ALERT values. Use the UP and DOWN arrows to
change values. Click SAVE when finished.
ChemLink
Home
Menu OneTouch
Help
Back
Status
Thu June 23, 2011 3:03 PM
ChemLink 1 pH
Status
Feeder
LIQUID
Feed TM
15 SEC
Delay OT
45 Min
Set Point
7.0
High Alert
8.0
Adjust
Low Alert
8.0
Page
Down
Page
Up
Save
Orp
pH
Default
8.4
Range
7.5 to 8.4
13.3.6 pH Alarm - Low Alert
The low alert alarm sets an alarm to deactivate the
controller in the event of a pH reading that is out of
low range. This could be an indication of a mechanical
malfunction in the feeding system.
On the CHEMLINK pH setup screen, select the LOW
ALERT setting. Use the UP and DOWN arrows to
change this setting. Click SAVE when finished.
ChemLink
Home
Menu OneTouch
Help
Back
Status
Thu June 23, 2011 3:03 PM
ChemLink 1 ORP
Status
Feeder
LIQUID
Feed TM
15 SEC
Delay OT
45 Min
Set Point
7.0
High Alert
8.0
Adjust
Low Alert
6.0
Page
Down
Page
Up
Save
Orp
pH
Default
6.8
Range
6.8 to 7.4
Page 58