19
3.2 I Installing the POD kit
The POD Kit is a measuring chamber using patented Quick Fix® technology for installation on a rigid 50 mm PVC pipe
(with supplied adapter) or 63 mm PVC pipe (without adapter). It contains the following components:
: Flow switch
:
pH sensor
:
ORP sensor
:
pH minus injection
:
Sensor holder
3.2.1 Recommended positioning
• The cell bypass valves must always be open.
• The sensor-holding POD kit must always be positioned on a horizontal pipe so that the sensors
are vertical.
• The POD kit must be the first unit fitted after the pool filter.
• If the pool is fitted with an electric heater, the POD kit must be installed upstream of the
heater (to take readings on unheated water).
• We recommend positioning the POD kit more than 20 cm from an elbow in the pipe.
• The sensor cables must not be positioned near high voltage mains electricity cables.
Recommended
pool grounding
Recommended
pool grounding
In-line installation
Installation on a by-pass
•
If an electric heater is installed (instead
of a heat pump), place the POD kit
before this heater (in order to measure
unheated water). In this case, the flow
switch must be placed on the bypass on
the fixture collar.
Recommended
pool grounding
Installation with a heating system
EN