SECTION 6 – OPERATION
The alarms are listed in the following table.
TABLE 16 -
ALARM LIST
BUTTON LABEL (ALARM
NAME)
CAUSE OF ALARM AND
CONDITION TO RESET
COUNTERMEASURES
Air Purge Blower Overcurrent
• The air purge blower motor
current exceeded the rated
value. The thermal relay
activated.
• Press the
ALARM RESET
button after you reset the
thermal relay.
Contact your local Johnson Controls Service Center.
Purge abnormal
• Purge tank pressure did not
fall to the automatic purge off
point while in automatic purge
operation.
• A rise in the purge tank
pressure was detected during
the automatic purge operation.
• The purge (vacuum) pump
motor current exceeded its
rated value. The thermal relay
activated.
• Press the
ALARM RESET
button after you reset the
pump motor thermal relay.
• Purge manually. See
• Contact your local Johnson Controls Service Center.
HG Hi Pressure Prevention
(HG (XG) high pressure
prevention control)
• The HG (XG) generator
pressure rose enough to
trigger the load limit operation
• The alarm is automatically
reset when the pressure falls
• Check the cooling water line.
• Check the cooling water flow rate.
• Check the cooling tower.
• Purge manually. See
• Contact your local Johnson Controls Service Center.
HG Hi Temperature Prevention
(HG (XG) high temperature
prevention control)
• The HG (XG) generator
solution temperature rose
enough to trigger the load limit
operation.
• The alarm is automatically
reset when the temperature
falls.
Low Cooling Water Inlet
Temp. (Low cooling water inlet
temperature (alarm))
• The cooling water inlet
temperature fell enough to
trigger the load limit operation
during the cooling operation
• The alarm is automatically
reset when the temperature
rises.
Check the cooling water inlet temperature control
system.
High Cooling Water Inlet
Temp. (High cooling water inlet
temperature)
• The cooling water inlet
temperature rose enough to
trigger the load limit operation
during the cooling operation
• The alarm is automatically
reset when the temperature
falls.
• Check the cooling water inlet temperature control
system.
• Check the cooling tower..
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...