JOHNSON CONTROLS
43
SECTION 3 – HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
FORM 155.33-ICOM2.EN.GB
ISSUE DATE:12/4/2017
4
ITEM
DISPLAY
UNIT
ADDRESS
CONTENT
MEASUREMENT
V
ALUE
15
Chilled / Hot water inlet temp.
12.0
°C
00083
0001~4000 unit, 1 unit=0.1 °C
16
Chilled / Hot water outlet temp.
7.0
°C
00085
0001~4000 unit, 1 unit=0.1 °C
17
Refrigerant temp. at evaporator
5.0
°C
00087
0001~4000 unit, 1 unit=0.1 °C
18
Cooling water inlet temp.
32.0
°C
00089
0001~4000 unit, 1 unit=0.1 °C
19
Cooling water outlet temp
37.0
°C
00091
0001~4000 unit, 1 unit=0.1 °C
20
Absorber solution temp.
38.0
°C
00093
0001~4000 unit, 1 unit=0.1 °C
21
High temperature generator
solution temp.
145.0
°C
00095
0001~4000 unit, 1 unit=0.1 °C
22
Exhaust gas temp.
220.0
°C
00097
0001~4000 unit, 1 unit=0.1 °C
23
High temperature generator
pressure
610
hPa
00099
0001~1100 unit, 1 unit=1 hPa
24
Motor opening rate
100
%
00101
0001~1100 unit, 1 unit=0.1%
25
High temperature generator
concentration
63
%
00103
0001~1100 unit, 1 unit=0.1%
26
Purge tank pressure
2.0
kPa
00105
0001~4000 unit, 1 unit=0.1 kPa
TABLE 9 -
WRITE COMMAND
ITEM
ADDRESS
CONTENT
1
Chiller-heater operation signal
02001
ON at Chiller-heater OPERATION, PULSE
SIGNAL
2
Chiller-heater stop signal
02002
ON at Chiller-heater STOP, PULSE SIGNAL
3
Set point
00203
0050~1000 unit, 1 unit=0.1°C
TABLE 8
- READ COMMAND (CONT'D.)
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...