JOHNSON CONTROLS
111
SECTION 7 – MAINTENANCE
FORM 155.33-ICOM2.EN.GB
ISSUE DATE:12/4/2017
7
STORAGE METHOD OF THE CHILLER-
HEATER
If the chiller-heater needs to be stored long-term, the
storage method varies. A lot depends on the machine
room temperature condition and the storage period. If
the machine room temperature is below 0 °C, drain off
the chilled / hot water, cooling water, and the waste hot
water. Dry the tube interiors. Make sure all equipment
installed in the chilled / hot water, cooling water, and
the waste hot water lines is completely dry.
Nitrogen gas pressurization inside the absorption chill-
er-heater is required when the storage period exceeds
6 months. Contact your local Johnson Controls Service
Center for more details.
The chiller-heater is not explosion proof.
Highly flammable items, gas, or liquids
should not be handled or stored near
the chiller-heater. Failure to do this may
result in explosion, injury, or damage to
the equipment or building.
There are two storage methods available for the chiller-
heater during off-season (winter) or plant suspension;
the wet storage method and the dry storage method.
The wet storage method is available only where chilled
/ hot water, cooling water, and waste hot water will not
freeze.
Each storage method has its own characteristics. Select
the method to use based on the plant’s features and the
storage period. Details follow.
WET STORAGE METHOD
The wet storage method may be used when there is no
concern about chilled / hot water, cooling water, and
waste hot water freezing in winter. Store the machine
in a place where the ambient temperature will remain
higher than 0 °C.
If it is likely that the temperature will drop below that,
provide a heater for the machine. If a heater is not pos-
sible, contact your local Johnson Controls service cen-
ter for further information. For details on the wet stor-
age method, see
.
The wet storage procedure is as follows if either the
chilled / hot water line, and/or the cooling water line is
an open system:
1. Completely drain the water if it has deteriorated
in quality.
2. Clean the water system by filling and draining
clear water through it from a position higher than
the chiller-heater.
3. Fill the water system with clear water.
4. Circulate the clear water through the water pump
(for 30 minutes to one hour) to clean it.
5. Drain the water.
6. Completely fill the water system with clear water
again.
7. Store the machine.
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...