JOHNSON CONTROLS
126
FORM 155.33-ICOM2.EN.GB
ISSUE DATE: 12/4/2017
SECTION 8 – TROUBLESHOOTING
TABLE 34 -
CHILLED WATER OVERCOOLING TROUBLESHOOTING
ITEM
CAUSE
COUNTERMEASURE
1
Chilled water flow rate drops or
changes suddenly
See if the chilled water flow rate changes suddenly (particularly
in case of variable flow rate specification). If it changes
suddenly, apply a limit of the change rate to the chilled water
flow or take another measure.
2
Cooling water temperature at the inlet
changes suddenly.
See if the cooling water at the inlet changes suddenly by
checking the start and stop of the fan. If the chilled water
temperature is low, the chiller-heater stops immediately. It
does not do the dilution process. If left as is, the solution may
crystallize in 4-5 hours. To prevent this, dilute the solution
according to the instruction shown in
Blowdown and Dilution Method on page 97
.
3
Load drops suddenly.
See if the load changes suddenly.
4
The refrigerant is dirty or contains
solution.
See if the refrigerant refining procedure has been performed
recently. See
Refrigerant Refining Method on page 97
for
more information.
5
Heat exchange tube is dirty (chilled
water)
Contact your local Johnson Controls Service Center.
6
Temperature controller or safety switch
is broken.
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...