SECTION 6 – OPERATION
BUTTON LABEL
(FAILURE NAME)
OPERATION
AT FAILURE
OCCURRENCE
CAUSE
COUNTERMEASURES
HG (XG) High
Pressure
Stop after dilution
HG (XG) pressure rose too high or too
quickly
• Check the cooling water line.
• Check the cooling water flow rate.
• Check the cooling tower
performance.
• Purge manually. See
.
• Contact your local Johnson Controls
Service Center.
HG (XG) High
temperature
HG (XG) solution temperature rose too
high or too quickly.
HG (XG) Low Liquid
Level
HG (XG) low liquid level was detected
during the exhaust gas input operation.
• Purge manually. See
.
• Contact your local Johnson Controls
Service Center.
Solution Circulation
P Abnormal (Solution
circulation pump
abnormal)
Stop without
dilution
Solution circulation pump motor current
exceeded the rated value and activated
the thermal relay. Or, the solution
circulation pump motor coil temperature
rose too high and activated the motor
overheat switch.
Contact your local Johnson Controls
Service Center.
Solution spray pump
abnormal
The solution spray pump motor current
exceeded the rated value and activated
the thermal relay. Or, the solution spray
pump motor coil temperature rose too
high and activated the motor overheat
switch.
Refrigerant pump
abnormal
Stop without
dilution
The refrigerant pump motor current
exceeded the rated value and activated
the thermal relay. Or, the refrigerant
pump motor coil temperature rose too
high and activated the motor overheat
switch.
TABLE 15
- FAILURE LIST, CONT'D
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...