SECTION 6 – OPERATION
On the Main screen, the lit buttons tell you which sys-
tems are running.
On the upper left of the screen below the
LOCAL
and
REMOTE
buttons is the Absorption (ABS) Machine
Status section with a group of buttons.
•
ABS Stop:
tells you if the absorption machine is
stopping.
•
ABS Operat.:
tells you if the absorption machine
is running.
•
Dilution:
tells you if the dilution process is ac-
tively running.
•
Thermo OFF:
the button lights if the chilled wa-
ter temperature falls or the hot water temperature
rises to the automatic stop temperature. It turns off
when the automatic restart condition is satisfied.
•
Solution Circulat. Pump:
tells you if the solu-
tion circulation pump is running or not.
•
Solution Spray Pump:
tells you if the solution
spray pump is running or not.
•
Refrig. Pump:
tells you if the refrigerant pump is
running or not.
•
Purge Pump:
tells you if the purge pump is run-
ning or not. In this example, it is not.
•
Waste Gas Input:
tells you if the waste gas input
is functioning or not.
•
Waste Hot Water Input:
tells you if the waste
hot water input is functioning or not.
•
Blower Fan:
tells you if the blower fan is operat-
ing.
•
Low Ref. Level:
tells you if the refrigerant level
is low.
On the right side of the screen the Related Equipment
Status section contains three buttons.
•
C / H W P Operat.:
tells you if the chilled / hot
water pump is operating or not.
•
Co W P Operat.:
tells you if the cooling water
pump is operating or not.
•
Engine Operat.:
tells you if the engine (or ex-
haust gas generation facility) is operating or not.
The Waste Gas Damper Status section contains the fol-
lowing sub-sections:
•
Inlet:
shows the status of the waste gas damper
installed at the waste gas inlet line.
•
Out.:
shows the status of the waste gas damper
installed at the waste gas outlet line.
•
Bypass:
tells you the status of the waste gas
damper installed at the waste gas bypass line.
•
Air:
shows the status of the air purge damper in-
stalled at the air purge line.
The lit buttons tell you which of the dampers are open
or closed.
Each of the sub-sections contains two buttons.
•
Fully Close:
tells you if the damper is closed.
•
Fully Open:
tells you if the damper is open.
The final section is the Waste Gas Supply Interrupting
Factor:
•
Waste Gas Forced Bypass:
the button is lit if the
waste exhaust gas input is interrupted while the
waste exhaust gas forced bypass switch is ON
•
Low Waste Gas Out. Temp.:
the button is lit the
waste exhaust gas input is interrupted due to a low
waste exhaust gas outlet temperature
•
Engine Startup Bypass:
the button is lit if the
waste exhaust gas input is interrupted due to the
bypass time after the engine starts.
•
Low Waste Gas In. Temp.:
the button is lit if the
waste exhaust gas input is interrupted due to a low
waste exhaust gas inlet temperature.
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...