SECTION 5 - COMMISSIONING
EG input stop
preparation starts
Bypass damper open
limit signal detected?
Air purge damper open
operation starts
Inlet damper close
operation starts
No
Air purge blower starts
FIGURE 23 -
EXHAUST GAS INPUT STOP PREPARATION FLOW DIAGRAM
Chiller-heater stops with
failure alarm
No
Chiller-heater stops with
failure alarm
Yes
Air purge damper open
limit signal detected?
Outlet damper close
operation starts
Inlet and Outlet
damper close limit signal
detected?
No
Chiller-heater stops with
failure alarm
Yes
Yes
Bypass damper open
operation starts
EG input stop preparation
completed