SECTION 7 – MAINTENANCE
EXHAUST GAS CONTAMINANTS
TABLE 20 -
EXHAUST GAS CONTAMINANTS
CONTAMINANT NAME
ALLOWABLE RANGE
MEASUREMENT METHOD
1
Soot
50 mg per Nm3
1
Dust density
2
Nitrogen Oxide
600 ppm
1
Chemiluminescence
2
3
Sulfur Oxide
0 ppm
Non dispersive Infrared gas
analyzer
2
4
Suspended particulate matter
0.5 mg per Nm3
• Liquid sampling
• Filter with membrane filter
• Weight
3
5
Solid carbide
0.5 mg per Nm3
• Filter sampling
• Weight
6
Oil
0.3 mg per Nm3
• Filter sampling
• Carbon tetrachloride extraction
• Infrared ray absorption spectrum
7
Ammonia
0 ppm
Indophenol blue absorptiometry
1. Or within local regulations
2. Converted with 0
2
equal to 0%
3. Not including a glass fiber-shaped material abundantly
Exhaust Gas Chimney Requirements
Each exhaust gas chiller-heater MUST have its own
chimney. This helps prevent the possible contamina-
tion of the chiller-heater by rust or other particulates
that may clog filters.
Содержание YHAU-CE-JE Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 120: ...JOHNSON CONTROLS 120 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 135: ...JOHNSON CONTROLS 135 FORM 155 33 ICOM2 EN GB ISSUE DATE 12 4 2017 9 THIS PAGE INTENTIONALLY LEFT BLANK...