After 30 seconds of operation, fans 1 & 3 (SYS 1, 5M &
7M), fans 5 & 7 (SYS 2, 11M & 13M), or fans 9 & 11
(SYS 3, 5M & 7M) or fans 13 & 15 (SYS 4, 11M & 13M)
will energize turning two additional fans on in the for-
ward direction. This is identical to standard fan control
by temperature (Page 76). These fans will de-energize
if ambient temperature drops below 40°F.
Pressure Control Only,
Fan Control by Discharge Pressure
Fan control by pressure will operate 4 stages of fan cycling
according to the discharge pressure of the corresponding
system. Ambient temperature will have no effect.
1. Until discharge pressure reaches 320 PSIG, no sys-
tem fans will operate.
2. When discharge pressure reaches 320 PSIG, fans 1
& 3 (SYS 1, 9M & 10M), fans 5 & 7 (SYS 2, 15M &
16M), fans 9 & 11 (SYS 3, 9M & 10M) or fans 13 &
15 (SYS 4, 15M & 16M) will be energized in the re-
verse direction. These fans will remain energized until
discharge pressure drops below 120 PSIG.
3. If discharge pressure reaches 340 PSIG, the revers-
ing fans on the respective system will be turned off.
At the same time, fans 2 & 4 (SYS 1, 6M & 8M), fans
6 & 8 (SYS 2, 12M & 14M), fans 10 & 12 (SYS 3, 6M
& 8M) or fans 14 & 16 (SYS 4, 12M & 14M) will ener-
gize. These fans will remain on until discharge pres-
sure drops below 120 PSIG.
4. If discharge pressure reaches 360 PSIG and com-
pressor run time has exceeded 30 seconds, fans 1
& 3 (SYS 1, 5M & 7M), fans 5 & 7 (SYS 2, 11M &
13M), fans 9 & 11 (SYS 3, 5M & 7M) or fans 13 & 15
(SYS 4, 11M & 13M) will energize turning the fans in
the forward direction. These fans will remain on until
discharge pressure drops to 140 PSIG.
Table 2 shows the operation of both modes of fan con-
trol previously discussed.
NOTE:
Fans with reversing contactors will have the reversing contactors mechanically and electrically locked out when the fans are
running forward. The forward contactor will also be locked out when the fans are running in reverse.
CONTROL BY
CONTROL BY
TEMPERATURE & PRESSURE
PRESSURE ONLY
SYS.
FAN
CONTACTOR
BELOW 25°F
ABOVE 25°F
TEMPERATURE
PRESSURE
TEMPERATURE
HAS NO EFFECT
CONTROL ONLY
CONTROL ONLY
ON
OFF
ON
OFF
ON
OFF
1
1 & 3 REV
9M & 10M
320 PSIG 120 PSIG
Will Not Start
35°F or
320 PSIG
120 PSIG
3
9 & 11 REV
9M & 10M
Above 25°F
340 PSIG
Turns OFF by
1
2 & 4
6M & 8M
340 PSIG
120 PSIG
25°F
Pressure Only at 340 PSIG
120 PSIG
3
10 & 12
6M & 8M
120 PSIG
1
1 & 3 FWD
5M & 7M
360 PSIG
140 PSIG
45°F
40°F
360 PSIG
140 PSIG
3
9 & 11 FWD
5M & 7M
2
5 & 7 REV
15M & 16M
320 PSIG
120 PSIG
Will Not Start
35°F or
320 PSIG
120 PSIG
4
13 & 15 REV
15M & 16M
Above 25°F
340 PSIG
Turns OFF by
2
6 & 8
12M & 14M
340 PSIG
120 PSIG
25°F
Pressure Only at 320 PSIG
120 PSIG
4
14 & 16
12M & 14M
120 PSIG
2
5 & 7 FWD
11M & 13M
360 PSIG
140 PSIG
45°F
40°F
340 PSIG
140 PSIG
4
13 & 15 FWD
11M & 13M
TABLE 2
LOW AMBIENT FAN CYCLING
Содержание YDAJ87HU7
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...