FORM 150.75-NM2
35
YORK INTERNATIONAL
DISPLAY KEYS
26572A(D)
DISPLAY
KEYS
GENERAL
The DISPLAY keys allow the user to retrieve system
pressures, system motor currents, chilled liquid tem-
peratures, outdoor ambient temperature, compressor
running times, number of compressor starts, and op-
tion information on the chiller package. This data is use-
ful for monitoring chiller operation, diagnosing potential
future problems, troubleshooting, and commissioning
the chiller.
Data will be displayed on a 40 character display con-
sisting of 2 lines of 20 characters. The display will up-
date all information at a rate of about 2 seconds. Real-
time data will be displayed for System 1 and 2 (Master
Module). System 3 (Slave Module) is not real time and
will only be updated every 10 seconds.
When a DISPLAY pushbutton is pressed, the corre-
sponding message will be displayed for the Master
Module and will remain on the display until another
pushbutton is pressed. If the same key is pressed again,
the corresponding message will be displayed for the
Slave Module or the other system.
NOTE: The AMBIENT TEMP, OPTIONS and WATER
TEMPERATURE keys will not display a sec-
ond set of data.
Display Messages may show characters indicating
greater than (>) or less than (<). These characters
indicate the actual values are greater than or less than
the limit values which are being displayed.
Each of the keys and an example of the typical corre-
sponding display messages will be discussed in the text
which follows.
Chilled Liquid Temp
A display indicating evaporator leaving and return water
temperature for the Master Module is provided when this
pushbutton is pressed.
When the key is pressed again, the display will be up-
dated for the Slave Module evap. water temps.
The minimum limit on the display is 8.7 DEG F. The
maximum limit on the display is 84.5 DEG F.
Ambient Temp
The outdoor ambient temperature is displayed when this
pushbutton is pressed.
The minimum limit on the display is 0 DEG F. The
maximum limit on the display is 133.8 DEG F.
CHILLED
LIQUID TEMPS
AMBIENT
TEMP
L W T 1
=
4 9 . 2
D E G F
R W T 1
=
5 2 . 0
D E G F
O U T S I D E
A M B I E N T
A I R
=
7 5 . 9
D E G F
L W T 2
=
4 9 . 2
D E G F
R W T 2
=
5 2 . 0
D E G F
Содержание YDAJ87HU7
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...