FORM 150.75-NM2
7
YORK INTERNATIONAL
OPERATIONAL LIMITATIONS
LD01911
CODE
MODEL
A
YDAJ87HU7, 87KU6, 97KU7
B
YDAJ88MU8, 98MU7, 99MU7, 99MW6, 99MW9
FIG. 3
COOLER WATER PRESSURE DROP
VOLTAGE LIMITATIONS
The following voltage limitations are absolute and op-
eration beyond these limitations may cause serious
damage to the compressor.
VOLTAGES
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
380-3-60
355
415
460-3-60
414
506
380/415-3-50
342
440
346-3-50
311
381
575-3-60
517
633
NOTES:
1. Units can be used for brine temperatures down to 20°F by
resetting standard control.
2. Operation below 25°F requires the Optional Low Ambient kit.
3. Operation above 115°F requires Optional High Ambient kit.
4. The evaporator is protected against freeze-up to -20°F with an
electrical heater cable as standard.
CAUTION: Excessive flow will cause damage to the
cooler. Do not exceed max. cooler GPM.
Special care should be taken when mul-
tiple chillers are fed by a single pump.
TEMPERATURES AND FLOWS
MODEL
LVG. WATER
COOLER
AIR ON
YDA
TEMP. °F
GPM
COND. - °F
Min.
1
Max.
Min.
Max. Min.
2
Max.
3
J87HU7
40
50
300
1280
0
130
J87KU6
40
50
400
1444
0
130
J97KU7
J88MU6
40
50
500
1606
0
130
J98MU7
J99MW6
40
50
500
1606
0
130
J99MU7
J99MW9
40
50
500
1606
0
130
Содержание YDAJ87HU7
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...