SECTION 33 - SYSTEM CALIBRATION, SERVICE SETPOINTS, AND RESET PROCEDURES
JCI COMPANY CONFIDENTIAL
JOHNSON CONTROLS
1. At the keypad, login at SERVICE access level us-
ing password 1 3 8 0.
2. From the MOTOR Screen, select the MOTOR
DETAILS Screen and enter the following set-
points using the procedures below.
Winding Temperature Protection
Enables the type of temperature sensing device used to
sense motor winding temperatures. Set to RTD when
the winding sensors are RTD's. Set to Thermistor when
the winding sensors are thermistors. Set to Disabled
when the motor is not equipped with winding tempera-
ture sensors or it is desired to disable the feature for
service reasons. The default setting is Disabled. To set
the appropriate type of temperature sensing device:
1. Press WINDING TEMPERATURE PROTEC-
TION key.
2. A dialog box appears with the selections.
3. Use
◄ and ►
keys to select Disabled, RTD or
Thermistor, as appropriate.
4. Press ENTER (
) key.
Bearing Temperature Protection
Enables the type of temperature sensing device used
to sense motor bearing temperatures. Set to RTD when
the bearing sensors are RTD's. Set to VSD Thermis-
tor when the bearing sensors are thermistors. Set to
Disabled when the motor is not equipped with bear-
ing temperature sensors or it is desired to disable the
feature for service reasons. The default setting is Dis-
abled. Select the appropriate sensing device as follows:
1. Press BEARING TEMPERATURE PROTEC-
TION key.
2. A dialog box appears with the selections.
3. Use
◄ and ►
keys to select Disabled, RTD or
VSD Thermistor, as appropriate.
4. Press ENTER (
) key.
Motor Vibration Protection
Enables and Disables the Motor Bearing Vibration
Protection feature. Set to Rolling Element when the
motor is equipped with bearing vibration sensors. Set
to Disabled when the motor is not equipped with bear-
ing vibration sensors or when it is desired to disable
the feature for service reasons. The default setting is
Disabled. To Enable or Disable the Motor Bearing Vi-
bration Protection feature:
1. Press MOTOR VIBRATION PROTECTION key.
2. A dialog box appears with the selections.
3. Use
◄ and ►
keys to select Disabled or Rolling
Element, as appropriate.
4. Press ENTER (
) key.
Cooling Coil Leak Detection
Enables the type of leak detection device used to detect
a leak of the motor cooling coil. Set to Optical when
the sensor is the optical type. Set to Float when the sen-
sor is the float type. Set to Disabled when the motor is
not equipped with leak sensors or for service reasons.
The default setting is Disabled. To enable the type of
leak detection:
1. Press MOTOR COOLING COIL LEAK PRO-
TECTION key.
2. A dialog box appears with the selections.
3. Use
◄ and ►
keys to select Disabled, Optical or
Float, as appropriate.
4. Press ENTER (
) key.
Manual Baseline
This setpoint is used to manually enter vibration base-
line values (0.1 to 5.0; Default 2) for the Shaft End
and Opposite Shaft End bearings. These values are not
in any particular units of measure. They are relative
values. The larger the number, the greater the magni-
tude of vibration represented. A special password is re-
quired. To enter the desired vibration baseline values:
1. Press MANUAL BASELINE key. A dialog box
appears requesting a special password.
2. Using numeric keypad keys, enter 0 3 6 8 and
press the ENTER (
) key. A green box appears
around the Shaft End vibration baseline value.
3. Press ENTER (
) key. A dialog box appears giv-
ing the range of values.
4. Using numeric keypad keys, enter the desired
value.
5. Press ENTER (
) key.
6. Using the
►
key, move the green box around the
Opposite Shaft End vibration baseline value.
7. Press ENTER (
) key. A dialog box appears giv-
ing the range of values.