291
SECTION 33 - SYSTEM CALIBRATION, SERVICE SETPOINTS, AND RESET PROCEDURES
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS
JCI COMPANY CONFIDENTIAL
33
TABLE 28 -
FLASH MEMORY CARD VERSION C.MLM.01.08.XXX
CHILLER STYLE/
COMPRESSOR
PROXIMITY
SENSE
OIL
HEATER
OUTPUT*
LEVEL
CONTROL
PERIOD
DEFAULT
FLOW
SWITCH
OIL-VARIABLE SPEED PUMP
PRESSURE SETPOINT NOT
ACHIEVED THRESHOLD*
“Style CDE/GHJ Compr”
Probe
TB1-34
3.5 sec
Digital
(Paddle Type)
35 psid
“Style E/P Compr”
Limit Switch
TB1-64
10.0 sec
Digital
(Paddle Type)
25 psid
“Style F/GH Compr”
Limit Switch
TB1-64
3.5 sec
Programmable
(Analog or Digital)
35 psid
“Style F/J Compr”
Probe
TB1-64
3.5 sec
Programmable
(Analog or Digital)
35 psid
“Style F/P, Compr”
Limit Switch
TB1-64
10.0 sec
Programmable
(Analog or Digital)
25 psid
NOTE:
* Not applicable to Style C (and earlier) chillers
TABLE 29 -
FLASH MEMORY CARD VERSION C.MLM.01.08.105A AND C.MLM.01.08.206A (AND LATER)
CHILLER STYLE/
COMPRESSOR
PROXIMITY
SENSE
OIL
HEATER
OUTPUT*
LEVEL
CONTROL
PERIOD
DEFAULT
FLOW
SWITCH
OIL-VARIABLE SPEED PUMP
PRESSURE SETPOINT NOT
ACHIEVED THRESHOLD*
“Style CDE/GHJ Compr”
Probe
TB1-34
3.5 sec
Digital
(Paddle Type)
35 psid
“Style E/P Compr”
Limit Switch
TB1-64
10.0 sec
Digital
(Paddle Type)
25 psid
“Style F/G, H5-8 Compr”
Limit Switch
TB1-64
3.5 sec
Programmable
(Analog or Digital)
35 psid
“Style F/J, H3 Compr”
Probe
TB1-64
3.5 sec
Programmable
(Analog or Digital)
35 psid
“Style F/P, Compr”
Limit Switch
TB1-64
10.0 sec
Programmable
(Analog or Digital)
25 psid
NOTE:
* Not applicable to Style C (and earlier) chillers
TABLE 30 -
SOFTWARE VERSION C.MLM.01.10B.XXX (AND LATER) OR C.OPT.01.10B.XXX (AND LATER)
CHILLER STYLE/
COMPRESSOR
PROXIMITY
SENSE
OIL
HEATER
OUTPUT*
LEVEL
CONTROL
PERIOD
DEFAULT
FLOW
SWITCH
OIL-VARIABLE SPEED PUMP
PRESSURE SETPOINT NOT
ACHIEVED THRESHOLD*
“Style CDE/GHJ Compr”
Probe
TB1-34
3.5 sec
Digital
(Paddle Type)
35 psid
“Style E/P Compr”
Limit Switch
TB1-64
10.0 sec
Digital
(Paddle Type)
25 psid
“Style F/G, H5-8 Compr”
Limit Switch
TB1-64
3.5 sec
Programmable
(Analog or Digital)
35 psid
“Style F/J, H3 Compr”
Probe
TB1-64
3.5 sec
Programmable
(Analog or Digital)
35 psid
“Style F/P, Q LH9
Compr”
Limit Switch
TB1-64
10.0 sec
Programmable
(Analog or Digital)
35 psid