89
SECTION 5 - MICROBOARD 031-03630-001
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS
JCI COMPANY CONFIDENTIAL
5
At the completion of the re-programming pro-
cess, if it is successful, “Flash Has Been Success-
fully Programmed” is displayed and “Operation
Successful” is displayed in the Status Code box.
Otherwise, a message in the status box indicates
the step that failed.
8. Remove power from OptiView Control Center.
9. Remove Program card from Microboard connec-
tor J26 by lightly pushing the SD card in and then
releasing pressure. The SD card should pop out
slightly allowing for removal.
10. Reposition Microboard DIP Switch SW1 position
4 to OFF.
11. Apply power to the OptiView Control Center. The