371
SECTION 36 - SOFTWARE ENHANCEMENTS
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS
JCI COMPANY CONFIDENTIAL
36
SI0252 - SOFTWARE ENHANCEMENTS (VER 23) EFFECTIVE MAY 2011 (CONT'D)
DIAGNOSTICS
COM2 RS-485 Port
In previous software versions, there was no serial port
loopback test for COM2 RS-485. This software ver-
sion adds a loopback test that operates like the other
loopback tests. It performs the test by transferring data
between COM2 and COM4a and comparing transmit-
ted data to received data. Pass/fail criteria is the same
as the other tests. The loopback connections are as fol-
lows:
TABLE 32 -
LOOP BACK CONNECTIONS
RS-485
FROM
TO
(COM 2/4a)
J13-8 (+)
J11-3 (+)
J13-10 (-)
J11-2 (-)
Install Microboard Program Jumpers JP17 and JP27 in
positions 1 and 2.
Digital I/O
When performing offline control of the outputs in Jap-
anese, Korean or Chinese, the SELECTION arrow is
replaced with a green box around the selected output.
DATE FORMAT
The calendar date can be displayed in three different
formats. Change the format using the new DATE FOR-
MAT setpoint on the USER screen, which can be done
at the operator access level. The selectable formats are:
• DD MMM YYYY (default)
• DD.MM.YYYY, or
• YYYY-MM-DD
SECURITY LOG – MANUAL RESET
WARNINGS
In previous software versions, a generic message
WARNING RESET was added to the security log
when any manual reset warning was acknowledged
(by pressing WARNING RESET). In this version, the
warning message that is being reset is entered as fol-
lows:
• Condenser or Evaporator Transducer Warning
• Standby Lube Low Oil Pressure Warning
• Excess Surge Detected Warning
• Condenser or VGD Sensor Failure Warning
• Conditions Override VGD Warning Reset
• Purge High Pressure Warning
• Purge Float Switch Error Warning
• Excess Purge Warning
• Purge Canister #X Full Warning
• Setpoint Override Warning
• Filter Not Running Warning