380
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 36 - SOFTWARE ENHANCEMENTS
JCI COMPANY CONFIDENTIAL
JOHNSON CONTROLS
NUMBER
DATA VALUE
HEADING TEXT
83
Filter L3 RMS Filter Current
Filter L3 Filter Cur
84
Filter L1 RMS Supply Current
Filter L1 Supply Cur
85
Filter L2 RMS Supply Current
Filter L2 Supply Cur
86
Filter L3 RMS Supply Current
Filter L3 Supply Cur
87
Filter Maximum Total Demand Distortion
Filter Max Demand
SSS DATA
#
Data Value
Heading Text
52
SSS Phase A Current
SSS Phase A Cur
53
SSS Phase B Current
SSS Phase B Cur
54
SSS Phase C Current
SSS Phase C Cur
55
SSS Phase A Voltage
SSS Phase A Volt
56
SSS Phase B Voltage
SSS Phase B Volt
57
SSS Phase C Voltage
SSS Phase C Volt
LCSSS DATA
#
Data Value
Heading Text
52
LCSSS Phase A Current
LCSSS Phase A Cur
53
LCSSS Phase B Current
LCSSS Phase B Cur
54
LCSSS Phase C Current
LCSSS Phase C Cur
55
LCSSS Phase A Voltage
LCSSS Phase A Volt
56
LCSSS Phase B Voltage
LCSSS Phase B Volt
57
LCSSS Phase C Voltage
LCSSS Phase C Volt
58
LCSSS Phase A Temperature
LCSSS Phase A Temp
59
LCSSS Phase B Temperature
LCSSS Phase B Temp
60
LCSSS Phase C Temperature
LCSSS Phase C Temp
Seal Lubrication Timer and Warning
When Standby Lube is enabled, seal lubrication is per-
formed by running the Oil Pump for two minutes. Seal
lubrication is performed once every twenty-four hours
since the Oil Pump was last run for at least two min-
utes. It was found that the twenty-four hour time period
could drift by several hours. This was corrected. Also,
the “Warning – Seal Lubrication In Progress” was
changed to be a non-annunciating warning.
Remote Analog Hot Water Setpoint
The Hot Water Setpoint on the Heat Recovery screen
did not control the remote analog signal when in Re-
mote Source at View Access level. The setpoint worked
properly in Service mode. This has been corrected to
work properly in all access modes.
SI0271 - SOFTWARE ENHANCEMENTS (VER 25) EFFECTIVE AUGUST 2013 (CONT'D)
TABLE 33 -
DATA LOGGING (CONT'D)