FORM 201.10-NM4
85
YORK INTERNATIONAL
3.3 AMBIENT TEMP KEY
When the Ambient Temperature key is pressed ambi-
ent air temperature as measured surrounding the chiller
is displayed.
Display Limits:
Minimum 4.6°F
(20.3°C)
Maximum 137.9°F (58.8°C)
3.4 SYSTEM PRESS / TEMP KEYS
Pressing one of the System Pressures / Temperatures
keys a number of times scrolls through six displays giv-
ing differential oil pressure (OIL), suction pressure (SP)
and discharge pressure (DP), suction (SUC) and dis-
charge (DSCH) temperature, oil temperature, saturated
discharge and suction temperature, compressor slide
valve position and compressor suction superheat.
Examples of these displays are as follows where # is
the appropriate system number:
Temperatures and pressures are either measured di-
rectly by transducers and temperature sensors, or com-
puted from these measurements as follows:
Differential oil pressure is the pressure difference be-
tween oil leaving the discharge separator and oil pres-
sure reaching the compressor. It is computed by sub-
tracting oil pressure measured after the oil line filter from
discharge pressure (oil in the oil separator is at discharge
pressure). Typically for a clean oil filter the drop will be
2 10 PSID (14 69 kPa) but may reach up to 40 PSID
(276 kPa).
S Y S
#
O I L =
1 5
P S I D
S P =
5 5
D P =
2 4 8
P S I G
S Y S
#
S U C
=
3 6 . 2
° F
D S C H
=
1 2 1 . 2
° F
O I L
T E M P #
=
7 7 . 9
° F
S A T
D S C H #
=
1 3 0 . 0
° F
S A T
S U C T #
=
2 4 . 3
° F
S Y S
#
S L I D E
V A L V E
P O S I T I O N
=
1 0 0 %
S Y S
#
S U P E R H E A T
=
1 2 . 2
° F
A M B I E N T
A I R
=
7 1 . 9
° F
Saturated discharge and suction temperatures are com-
puted by converting measured pressure to temperature.
Slide Valve Position is computed from average % FLA
motor current, discharge pressure and the number of
load pulses sent to the compressor.
NOTE: Slide valve position is
approximate
and should
be used for reference only. Under many condi-
tions, it will read well below 100%, possibly as
low as 60%, when a compressor is fully loaded.
Superheat is computed by subtracting saturated suc-
tion temperature from suction temperature.
Display Limits are as follows for the System Pressures
and Temperature displays are as follows:
NOTE: Minimum and maximum values may change as
software (EPROM) revisions are made.
NOTE: *Below 9.0°F the Suction Temp. display will dis-
appear. This will in turn cause the Superheat
display to disappear.
3.5 % MOTOR CURRENT KEY
Pressing the Percentage Motor Current key a number
of times scrolls through displays of compressor current
for each system, ISN/EMS current limits and ISN lag
compressor start percentage. Example displays and
detailed explanations are as follows:
This display shows the average compressor motor cur-
rent and each individual phase current (L1, L2, and L3)
on each compressor as a percentage of FLA. All val-
ues are approximate.
MIN. LIMIT
MAX. LIMIT
Oil Pressure
208 PSID
0 PSID
Suction Pressure
0 PSIG
199 PSIG
Discharge Pressure
0 PSIG
399 PSIG
Suction Temp.
*9.0°F
84.2°F
Discharge Temp.
40.3°F
302.6°F
Oil Temp.
40.3°F
240.0°F
Sat. Discharge Temp.
41.0°F
140.5°F
Sat. Suction Temp.
41.0°F
101.3°F
Slide Valve Position
0%
100%
Suction Superheat
*81.5°F
60.9°F
C O M P # = A V G ; P H
L , 1 , 2 , 3
1 0 0 ;
9 9 , 1 0 1 , 1 0 1
% F L A
Содержание Millennium YDAS 410