FORM 201.10-NM4
55
YORK INTERNATIONAL
FIG. 30
YDAS 410 - 490 (SYSTEMS 1 & 2) ELEMENTARY DIAGRAM ACROSS-THE-LINE START (CONTD)
ELEMENTARY DIAGRAM
CAUTION:
No Controls (relays, etc.)
should be mounted in the
Smart Panel enclosure or
connected to power sup-
plies in the control panel.
Additionally, control wiring
not connected to the Smart
Panel should not be run
through the cabinet. This
could result in nuisance
faults.
CAUTION:
Any inductive devices (re-
lays) wired in series with
the flow switch for start/
stop, into the Alarm cir-
cuitry, or pilot relays for
pump star ters wired
through motor contactor
auxiliary contacts must be
suppressed with YORK
P/N 031-00808-000 sup-
pressor across the relay/
contactor coil which acti-
vates the contacts.
Any contacts connected to
flow switch inputs or BAS
inputs on terminals 13 - 19
or TB3, or any other termi-
nals, must be suppressed
with a YORK P/N 031-
00808-000 suppressor
across the relay/contactor
coil which activates the
contacts.
CAUTION:
Control wiring connected to
the control panel should
never be run in the same
conduit with power wiring.
MAX
NON-
CONTROL
MIN
DUAL
FUSED
UNIT
POWER
CIRCUIT ELEMENT
DISC.
VOLTAGE
SUPPLY
AMP.
FUSE
SWITCH
SIZE
SIZE
ALL MODELS
115-1-50/60
20A
20A 250V
30A 240V
W/O TRANS.
MODELS
-17
200-1-60
15A
15A 250V
30A 240V
WITH
-28
230-1-60
15A
15A 250V
30A 240V
TRANS.
-46
400-1-60
8A
8A 600V
30A 480V
*
- 5 8
575-1-60
8A
8A 600V
30A 600V
* All primary and secondary wiring between transformer and control panel included.
CONTROL POWER SUPPLY
LD02041
Содержание Millennium YDAS 410
Страница 135: ...FORM 201 10 NM4 135 YORK INTERNATIONAL ...