YORK INTERNATIONAL
100
This display shows the Target temperature programmed
at the time of the fault.
This message indicates the surrounding Ambient Air
Temperature at the time of the fault.
This display shows the Low Ambient Cutout pro-
grammed at the time of the fault.
This display shows the Low Suction Pressure Cutout
programmed at the time of the fault.
This message indicates which system was acting in lead
in the Master Section of the chiller at the time of the
fault; in this case System 1.
This message indicates which system was acting as
the lead in the
Subordinate
section of the chiller at the
time of
the fault; in this case, System 3.
This message shows whether remote or local commu-
nications was selected at the time of the fault.
System Data:
Pressing Enter again gives the following message:
This advises that the common data has been completed
and that pressing the Enter key will now scroll through the
system history data for the master section of the chiller, i.e.
the data for System 1 followed by the data for System 2.
The data for each system is provided through twenty
information displays as described under YCAS 2 Sys-
tem Models System Data above.
After completing the system data for the master sec-
tion, pressing Enter again gives the following message:
Pressing the Enter key will now scroll through the sys-
tem data for System 3, then System 4, as for Systems
1 and 2 above.
At the end of this sequence, the display scrolls back to the
request to select a safety shutdown number to display.
4.7 FAULT HISTORY DATA REMOTE PRINTOUT
The following text shows a typical example printout ob-
tained by pressing the History key with an optional printer
attached. In this case an example is given for a YCAS 3
System Chiller. YCAS 2 System Models and YDAS mod-
els provide similar printouts for the appropriate number
of system:
YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
ISN OPTION ENABLED
SOFTWARE VERSION C.A12.03.01
SAFETY SHUTDOWN NUMBER 1
SHUTDOWN @ 1:36PM 2/4/98
CHILLER FAULT:
VAC UNDER VOLTAGE SHUTDOWN
RETURN WATER TEMP
45.7 DEGF
LEAVING WATER TEMP
44.4 DEGF
LOW WATER CUTOUT
36.0 DEGF
COOLING RANGE
41.0 TO 44.6 DEGF
TARGET TEMP
42.8 DEGF
AMBIENT AIR TEMP
78.1 DEGF
LOW AMBIENT CUTOUT
25.0 DEGF
LOW PRESSURE CUTOUT
44.0 PSIG
LEAD SYSTEM
SYS 3
LOCAL REMOTE SETTING:
LOCAL
SYSTEM 1 DATA
COMPRESSOR STATUS
OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
AVERAGE MTR = 0
0 %FLA
PHASE L1 MTR = 0
0 %FLA
PHASE L2 MTR = 0
0 %FLA
PHASE L3 MTR = 0
0 %FLA
DIFF OIL PRESSURE
0.0 PSID
SUCTION PRESSURE
76.2 PSIG
SATURATED SUCTION
45.1 DEGF
SUCTION TEMP
46.2 DEGF
SUPERHEAT
1.1 DEGF
DISCHARGE PRESSURE
113.0 PSIG
SATURATED DISCHARGE
64.6 DEGF
DISCHARGE TEMP
66.4 DEGF
OIL TEMP
100.9 DEGF
LIQUID INJECTION VALVE
OFF
FORWARD FANS
OFF
REVERSE FANS
OFF
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
P R E S S
E N T E R
T O
D I S P L A Y
S
U B
D A T A
T A R G E T
T E M P
4 4 . 0
° F
A M B I E N T
A I R
T E M P
7 7 . 6
° F
L O C A L
R E M O T E
S E T T I N G
L O C A L
L O W
P R E S S U R E
C U T O U T
4 4
P S I G
P R E S S
E N T E R
T O
D I S P L A Y
M A S T E R
D A T A
L O W
A M B I E N T
C U T O U T
2 5 . 0
° F
M A S T E R
L E A D
S Y S T E M
S Y S
1
S
U B
L E A D
S Y S T E M
S Y S
3