FORM 201.10-NM4
71
YORK INTERNATIONAL
RANGE and press the ENTER key to store the new
value in memory.
Alarm Contacts (Annunciation Alarm)
Internal contacts are provided on Terminals 23 & 24 of
TB1 in the Power Panel (See Section 1.9) which can be
used to remotely signal a warning whenever a fault lock-
out occurs on any system or if power is lost to the con-
trol panel. The internal contacts are normally open (N.O.)
and will close when control power is applied to the panel,
if no fault conditions are present. When a fault occurs
or power is lost, the contacts open.
A 28VDC or 120VAC (60 Hz models) or up to 240VAC
(50 Hz models) external alarm circuit (supplied by oth-
ers) should be wired into the alarm contact terminals to
use this feature. The contacts are rated at 125VA.
NOTE: If any inductive load devices (relay or contac-
tor) supplied by the user are in the electrical
circuit connected to the dry alarm contacts, the
device must be suppressed at the load with a
RC suppressor YORK Part Number 031-00808-
000 across the inductive coil. (Typically, sev-
eral are supplied loose with the panel.) Failure
to install suppressors will result in nuisance
faults and possible damage to the chiller.
NOTE: If the alarm circuit is applied in an application
used for critical duty (such as process duty or
cooling other critical equipment) and the alarm
circuit should fail to function, YORK will not be
liable for damages.
1.8
MICROPROCESSOR BOARD LAYOUT
3
5
2
1
4
ITEM
DESIGNATION
DESCRIPTION
1
J18
Clock Enable/Disable Jumper
2
RTC (U13)
Real Time Clock and Battery Backup I.C. (031-00955-000)
3
EPROM
Microprocessor I.C. (Label shows version)
Note: Dimple is positioned at top edge
4
S1
Dip Switch Set (8 switches)
5
S2 to S5
System Switches S2 = System 1, S3 = System 2, S4 = System 3, S5 = System 4
FIG. 38
MICROPROCESSOR BOARD LAYOUT
26001A
DIMPLE (AT TOP)
MASTER EPROM
031-01714-105
SUBORDINATE
EPROM
031-01714-105