FORM 201.10-NM4
9
YORK INTERNATIONAL
LD03802
TEMPERATURES AND FLOWS
1440 - 1722 kW
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 11°C, contact your nearest YORK office for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°F with an electrical heater as standard.
4. Operation above 46.1°C requires the Optional High Ambient Kit.
5. YDAS Units have two coolers in parallel.
FIG. 2B – COOLER WATER PRESSURE DROP, TOTAL (SI)
OPERATIONAL LIMITATIONS
(SI)
VOLTAGE LIMITATIONS
The following voltage limitations are ab-
solute and operation beyond these limita-
tions may cause serious damage to the
compressor.
VOLTAGES
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
460-3-60
414
506
575-3-60
517
633
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (°C)
(L/S)
3
CONDENSER (°C)
YCAS & YDAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX.
4
410
4.4
11.1
31.5
5
101.3
5
-17.7
54.4
440
4.4
11.1
31.5
5
101.3
5
-17.7
54.4
470
4.4
11.1
31.5
5
101.3
5
-17.7
54.4
490
4.4
11.1
31.5
5
101.3
5
-17.7
54.4
MODEL YDAS
COOLER CODE
410, 440, 470, 490
4
Содержание Millennium YDAS 410