YORK INTERNATIONAL
14
MODELS YDAS 410 - 490
(SI Units)
LD01608
LD01607
NOTES:
1. Clearances - Recommended YORK clearances for peak performance, reliable operation and maintenance:
Side to wall 2438 mm*; Rear to wall 2438 mm; Control Panel End to wall 1524 mm*; Over the top - No obstructions allowed; Distance
between adjacent units 3658 mm, (Walls should be no higher than the unit.)
*No more than one high wall can be higher than the top of the unit. The area within the clearances shown above and area under the unit
must be kept clear of all obstructions or clutter that would impede air flow through the unit. In installations where winter operation is
intended and snow accumulations are expected, additional unit height must be provided to insure air flow.
NOTE: Reduced clearances may be used due to jobsite restrictions. The unit will unload to prevent the condenser pressure and motor
current from exceeding the maximum limits and will continue to operate without nuisance high-pressure or motor-current cutouts
even though the air flow may be restricted at these conditions.
2.
Cooler liquid connection sizes (inlet and outlet): 8" victaulic for all models.
3. Spring isolators (OPTIONAL) will increase overall height of unit.
FIG. 5
MODEL YDAS 410 - 490 DIMENSIONS (SI UNITS)