YORK INTERNATIONAL
118
stead of % FLA. The System # Motor Current at 100%
FLA value is password protected.
The FLA value at the specified conditions varies with
compressor model and supply voltage. These values
are given for each system on each chiller model for each
supply voltage in the tables in Section 8.4.
To program the System # Motor Current at 100% FLA,
begin with System 1 (the # on the sample display will
read 1) and key in the value given in the table, then
press the Enter key to store the value into memory and
scroll the display on to the next system. Now key in the
value given in the table for System 2, then repeat for
System 3 and System 4 where appropriate. After all
systems have been programmed the display will scroll
to the next programmable control setting.
Liquid Injection Temperature Limit
The Liquid Injection Temperature Limit setting is the
compressor discharge gas temperature above which
the liquid injection solenoid is energized to allow liquid
injection into the compressor to limit discharge gas tem-
perature and hence oil system temperature. This is used
to maintain the oil within the correct temperature range
to provide proper lubrication and cooling of the com-
pressor mechanical parts.
Once liquid injection is activated, discharge temperature
must fall 20°F below the temperature limit before injec-
tion is deactivated. A setting of 180°F is recommended
for this control for most applications. This programmable
value is password protected.
To program the Liquid Injection Temperature Limit, key
in the required setting and press the Enter key to store
the value into memory and scroll to the next display.
Condensing Temperature Full Load Setting
If load equalization utilizing % Slide Valve is selected
(See Load Sharing Basis later in this section), the mi-
cro must be programmed with the design condensing
temperature (discharge pressure converted to tempera-
ture or CTP) at 100% load at design conditions for each
system on the chiller. This also allows the micro to cal-
culate approximate compressor slide valve position
which is important when controlling load sharing be-
tween compressors. The System # Condensing Tem-
perature at 100% Load valve is password protected.
The allowable range of Condensing Temperature at
100% Load is 100 - 140°F with the default set for 125°F.
The value which must be programmed varies with chiller
and compressor model. Values for each system on each
chiller model are given in the tables in Section 8.5.
To program the System # Condensing Temperature at
100% Load, begin with system 1 (the # on the sample
display will read 1) and key in the value given in the table,
then press the Enter key to store the value into memory
and scroll the display on to the next system. Now key in
the value given in the table for System 2, then repeat for
System 3 and System 4 where appropriate. After all sys-
tems have been programmed, the display will scroll to
the next programmable control setting.
Communications Mode
If an ISN system or an optional Remote Control Center
(RCC) is connected to the chiller, the Communications
Mode value is used to select the correct type of com-
munication protocol required.
To program the Communications Mode, key in the num-
ber corresponding to the connected device (1=ISN,
2=RCC), then press the Enter key to store the value
into memory and scroll to the next display.
Load Sharing Basis
Equalized loading / unloading of compressors to give
the maximum chiller efficiency is based on the calcu-
lated loading of each running compressor. This calcu-
lation can in turn be based on either the estimated com-
pressor slide valve position, or the % of full load current
being drawn by the compressor motor. The Load Share
Based On ? value determines which basis is used by
the micro for its calculations.
The % FLA method is suitable for most applications
and is the default setting for this control. Where signifi-
cant running in low ambient temperature conditions is
expected, however, more accurate load equalization will
be achieved using the % Slide Valve method which in-
cludes discharge pressure in the calculation.
To program the Load Share Based On ?, key in the
number corresponding to the connected device (1=%
Slide Valve, 2=% FLA), then press the Enter key to store
the value into memory and scroll to the next display.
L I Q U I D
I N J E C T I O N
T E M P
L I M I T
=
1 8 0 . 0 ° F
S Y S T E M
#
C O N D
T E M P
1 1 9 . 0
° F
=
1 0 0 %
L O A D
C O M M U N I C A T I O N S
M O D E
1
=
I S N ,
2
=
R C C ,
2
L O A D
S H A R E
B A S E D
O N ?
1
=
S V % ,
2
=
% F L A
2