FORM 201.10-NM4
133
YORK INTERNATIONAL
PROBLEM
CAUSE
SOLUTION
Compressor Won’t Load
1. Demand not great enough.
1. No problem. Consult
Installation Manual to aid
in understanding
compressor operation.
2. Low oil pressure.
2. Check oil circuit.
Assure oil load solenoid
valve is working.
Assure that discharge
pressure is at least
50 pounds over suction.
Contact the local YORK
service representative.
3. Defective water
3. Compare the display with
temperature sensor.
a thermometer. Should be
or - 2 degrees.
Lack of Cooling Effect
1. Fouled evaporator surface.
1. Contact the local YORK
Low suction pressure
service representative.
will be observed.
2. Improper flow through the
2. Reduce flow to within
evaporator.
chiller design specs.
3. Low refrigerant charge.
3. Check subcooling and
Low suction pressure
add charge as needed.
will be noted.
“PHASE ROTATION” FAULT
1. Chiller wiring phased
1. Rewire chiller wiring.
incorrectly.
“MOTOR CURRENT
1. Incoming voltage not
1. Resolve incoming voltage
UNBALANCE”
balanced phase to phase.
imbalance.