YORK INTERNATIONAL
120
A List of the default values entered into memory, if this
program option is selected, is shown below:
6140
PROGRAMMABLE VALUE
DEFAULT
SETTING
Discharge Pressure Cutout
R22
399 PSIG
R134a
275 PSIG
Low Ambient Cutout
Std. Amb.
25°F
Low Amb.
0°F
High Ambient Temp. Cutout
100°F
Discharge Pressure Unload
R22
375 PSiG
R134a
255 PSIG
Average Current Unload
105%
Anti-Recycle Timer
600 sec.
Leaving Chilled Liquid Cutout
36°F
Suction Pressure Cutout
R22
44 PSIG
R134a
19 PSIG
Lag Panel Start Pt (YDAS Only)
50%
Lag Panel Diff. Off (YDAS Only)
20%
Lag Compressor Start Point
70%
Lag Compressor Differential Off
50%
Fan Control Discharge Pressure
R22
230 PSIG
Pressure Setpoint
R134a
102 PSIG
Fan On / Off Differential
R22
50 PSIG
R134a
50 PSIG
System Motor Current
Liquid Injection Temperature Limit
108°F
System Full Load Condenser Temp.
Communications Mode
2
Load Share Based On ?
2
Economizer Valve On Point
50%
Economizer Valve Off Point
40%