PROBLEM
CAUSE
SOLUTION
“LOW SUCTION PRESSURE”
1. Improper suction pressure
1. Adjust per recommended
FAULT
cut-out adjustments.
settings.
2. Low refrigerant charge.
2. Repair leak if necessary
and add refrigerant.
3. Fouled filter dryer.
3. Change dryer core.
4. EEV defective
4. Replace EEV.
5. Reduced flow of chilled
5. Check GPM (See
liquid through the cooler.
OPERATION
LIMITATIONS)
Check operation of pump,
clean pump strainer, purge
chilled liquid system of air.
6. Defective suction pressure
6. Replace transducer or
transducer or faulty wiring.
repair wiring.
“HIGH DISCHARGE
1. Condenser fans not
1. Check fan motor, fuses,
PRESSURE” FAULT
operating or operating
and contactors.
backwards.
Assure forward fan blow
NOTE: If a mechanical high
air upward.
pressure cut-out opens,
the system will shut down
2. Too much refrigerant.
2. Remove refrigerant.
on low motor current.
3. Air in refrigerant system.
3. Evacuate and recharge
system.
4. Defective discharge
4. Replace discharge
pressure transducer.
pressure transducer.
5. Assure outdoor ambient
5. Verify displayed ambient
sensor is reading correctly.
temperature is within
+ or - 15°F of
thermometer placed
next to sensor.