FORM 201.10-NM4
87
YORK INTERNATIONAL
SWITCH 2: Ambient Temp. Low Limit
Open:
Standard Ambient Mode fixes the Low Ambient Cut-
Out setting at 25°F (3.9°C) and is not adjustable.
Closed:
Low Ambient Mode allows the Low Ambient Cut-Out to
be programmed from 0 to 50°F. Values above 25°F can
be used to automatically shut down the chiller when di-
rect cooling methods become operational.
SWITCH 3: Chiller Control
Open:
Local Control Mode allows an ISN system or an RCC
(Remote Control Center) panel to receive chiller data
from the chiller through the RS-485 port, but not change
programmable setpoint values remotely.
Closed:
Remote Control Mode allows an ISN system or an RCC
(Remote Control Center) panel to receive chiller data
from the chiller through the RS-485 port. This mode will
also allow programming of loading, unloading, shut-
down, Leaving Water Setpoint Reset, Current Limit
Setpoint, and Lag Start Setpoint from an ISN or RCC. If
communications are lost to the ISN or RCC, the micro
will run the chiller on the locally programmed values.
SWITCH 4: Expansion Valve Type
Both Positions:
This switch is presently disabled. In the future, it will
allow selection of control from either thermal expan-
sion valves or electronic expansion valves.
SWITCH 5: Units of Measurement
Open:
English Units Mode causes all information relating to
pressures, temperatures, etc., to be displayed in En-
glish (Imperial) units (°F, PSI, etc).
Closed:
S.I. Units Mode causes all information relating to pres-
sures, temperatures, etc., to be displayed in S.I. (Met-
ric) units (°C, BAR, etc.). For conversion purposes,
1BAR = 14.5 PSIG.
SWITCH 6: Compressor Motor Starting
Open:
Across-The-Line Mode MUST be used for chillers with
single contactor Across-the-Line (A.C.L.) starters on
each compressor.
Closed:
Wye-Delta Mode MUST be used for chillers with multi-
contactor and resistor Wye-Delta (Star/Delta) closed
transition starters on each compressor.
SWITCH 7: Compressor Lead/Lag
Open:
Manual Lead / Lag Mode allows selection of the com-
pressor or compressor group lead / lag sequence us-
ing external contact closure.
The manual lead / lag selection is automatically over-
ridden (causing the lag compressor / group to become
the lead) any time the selected lead compressor / group
R E M O T E
C O N T R O L
M O D E
A C R O S S - T H E - L I N E
M O T O R
S T A R T I N G
L O C A L
C O N T R O L
M O D E
S I
U N I T S
R E A D O U T
E N G L I S H
U N I T S
R E A D O U T
T H E R M A L
E X P A N S I O N
V A L V E S
S T A N D A R D
A M B I E N T
L O W
A M B I E N T
C O N T R O L
W Y E
D E L T A
M O T O R
S T A R T I N G
M A N U A L
L E A D
/
L A G