YORK INTERNATIONAL
90
4. PRINT KEYS
28164(B)A
4.1 GENERAL
The Print keys provide access to two sets of informa-
tion either locally on the panel display, or, if an optional
printer is connected, remotely as hard copy printouts.
The Operating Data key provides a real-time list of sys-
tem operating data and programmed settings. The His-
tory key provides a comprehensive list of operating data
and programmed settings at the instant of fault on each
of the last nine faults (local display) or three faults (re-
mote printout) which occurred on the chiller.
4.2 OPER DATA KEY
If a remote printer is not connected, pressing the Oper-
ating Data key allows the user to scroll through infor-
mation, on the 40 character display, which is not directly
available from the Display keys on the panel.
If a remote printer is connected, pressing the Operating
Data key causes a snapshot to be taken of system oper-
ating conditions and of the user programming selections.
The data is stored in temporary memory, then transmit-
ted from the Microprocessor to the remote printer. As
the data is transmitted, it is erased from the memory.
Information available using the Operating Data key is de-
scribed in the following sections. In example displays, #
is used to indicate system number where appropriate:
4.3 OPERATING DATA LOCAL DISPLAY MESSAGES
YCAS 2 SYSTEM MODELS:
When the Operating Data key is pressed, the following
message appears:
Repetitively pressing the Enter key will then scroll
through the following Common (whole chiller) Data and
individual System Data information displays:
Common Data:
This message shows the time remaining on the Load
Timer and the Unload Timer. Timers constantly recycle
and are used in conjunction with rate control and tem-
perature deviation from setpoint to determine when
loading should occur.
NOTE: These timers may appear not to count accord-
ing to actual time. This is normal and is con-
trolled by the micro to compensate for chang-
ing loading requirements.
P R E S S
E N T E R
T O
D I S P L A Y
D A T A
L O A D
T I M E R
7 0
S E C
U N L O A D
T I M E R
6 0
S E C