< 6. Maintenance Functions >
6-4
TI 34M6A82-01E
2nd Edition : Nov. 1, 2002-00
Message Code
Description
Trouble-shooting
Sub-unit
transmitter
error
12-0000
Cannot read/write to the module installed in
the sub-unit
• Turn ON the sub-unit
power supply
• Check the optical FA
bus or the optical FA
bus 2 cables
Sub-unit
transmitter
switching has
occurred
13-0000
Transmitter cable breakage in loop-
connected remote I/O system
• Replace the optical FA
bus or the optical FA
bus 2 cables
Sensor control
block scan
timeout
14-0000
Exceeded the scan time monitoring period of
the sensor control block
Modify the program.
*********** XX-XXXX
An undefined error has occurred