92
Factory Settings
Terminal Functions for 3-wire Sequence Selection
When 0 is set for terminal S3 (n052), terminal S1 is the RUN command,
terminal S2 is the STOP command, and terminal S3 is the FWD/REV
RUN command.
To select the 3-wire sequence, set terminal S3 (n052)
to 0.
Failure to observe this warning may result in injury.
LOCAL/REMOTE Selection (Setting: 17)
Select the operation reference from either the Digital Operator or from
the settings of the RUN Command Selection (n003) and Frequency Ref-
erence Selection (n004). The LOCAL/REMOTE Selection can be used
only when stopped.
Open:
Run according to the setting of RUN Command Selection
(n003) or Frequency Reference Selection (n004).
Closed: Run according to the frequency reference and RUN command
from the Digital Operator.
No.
Terminal
Factory Setting
Function
n050
S1
1
FORWARD RUN command
(2-wire sequence)
n051
S2
2
REVERSE RUN command
(2-wire sequence)
n052
S3
3
External fault (NO contact input)
n053
S4
5
Fault reset
n054
S5
6
Multi-step speed reference 1
n055
S6
7
Multi-step speed reference 2
n056
S7
10
JOG command
RUN Command
(Run when Closed)
STOP Command
(Stop when Open)
FWD/REV Run Selection
FWD Run When Open
REV Run When Closed
RUN SW
(NO Contact)
STOP SW
(NC Contact)
VS-606V7
WARNING