6. Programming Features
117
• Simultaneous Broadcasting Data (available only for write in)
Bit signals not defined as the broadcast operation signals are used as
the local station data signals.
• Monitor Data (available only for read out)
Register
No.
Bit
Description
0001H
0
RUN command
1: Run
0: Stop
1
Reverse run
1: Reverse run
0: Forward run
2
(Not used)
3
(Not used)
4
External fault
1: Fault (EFO)
5
Fault reset
1: Fault reset command
6-F
(Not used)
0002H
Frequency reference 30000/100 % fixed unit
(Data is converted into 0.01 Hz inside the Inverter, and fractions
are rounded off.)
Register
No.
Bit
Description
0020H
S
tatus signal
0
RUN command
1: Run
0: Stop
1
Reverse run
1: Reverse run
0: Forward run
2
Inverter operation
ready
1: Ready
0: Not ready
3
Fault
1: Fault
4
Data setting error
1: Error
5
Multi-function output 1 (1: MA ON
0: MA OFF)
6
Multi-function output 2 (1: P1 ON
0: P1 OFF)
7
Multi-function output 3 (1: P2 ON
0: P2 OFF)
8-F (Not used)