120
002CH
In
verter st
at
us
0
Run
1: Run
1
Zero-speed
1: Zero-speed
2
Frequency agreed
1: Agreed
3
Minor fault (Alarm is indicated)
4
Frequency detection 1
1: Output frequency
≤
(n095)
5
Frequency detection 2
1: Output frequency
≥
(n095)
6
Inverter operation ready
1: Ready
7
Undervoltage detection
1: Undervoltage detection
8
Baseblock
1: Inverter output baseblock
9
Frequency referecne mode 1: Other than communications
0: Communications
A
RUN command mode
1: Other than communications
0: Communications
B
Overtorque detection
1: Detection or overtorque fault
C
Undertorque detection
1: Detection or undertorque fault
D
Fault retry
E
Fault (Including MEMOBUS communications timeover)
1: Fault
F
MEMOBUS communications timeover 1: Timeover
002DH
Mult
i-f
un
cti
o
n
ou
tpu
t
0
MA
1: ON
0: OFF
1
P1
1: ON
0: OFF
2
P2
1: ON
0: OFF
3-F (Not used)
002EH
In
ver
te
r
S
tat
us
0
Frequency reference loss 1: Frequency reference loss
1-F (Not used)
002FH-
0030H
Reserved
0031H
Main circuit DC voltage (1/1 V)
0032H
Torque monitor (1/1 % ; 100 %/Motor rated torque ; with sign)
0033H-
0036H
(Not used)
0037H
Output Power (1/1 W: with sign)
Register
No.
Bit
Description