210
Note: 1. Not initialized by constant initialization.
2. Upper limit of setting range and factory setting are doubled for 400 V
Class.
3. Depends on Inverter capacity. Refer to the next page.
4. Depends on Inverter capacity. Refer to page 84.
5. Factory setting of the model with JVOP-147 Digital Operator (with-
out potentiometer) is 1. Setting can be set to 0 by constant initializa-
tion.
6. When control mode selection (n002) is changed, factory setting corre-
sponds to the control mode. Refer to the next page.
7. Depends on Inverter capacity. Refer to page 125.
8. Constant that is provided for 5.5 kW and 7.5 kW Inverters of 200-V
and 400-V classes
9. 1 (Enabled) for 5.5 kW and 7.5 kW Inverters of 200-V and 400-V
classes
10. Do not select 3 to 100 as they are reserved for future use.
169
01A9
Output Open-phase Detection
Time
0.0 to 2.0 s
0.1 s
0.0 s
No
152
170
#1
01AA
ENTER command operation
selection (MEMOBUS com-
munications)
0, 1
-
0
No
121
171
#1
01AB
Frequency reference bias up-
per limit (UP/DOWN com-
mand 2)
0.0 to 100.0%
(n011/100%)
0.1%
0.0%
Yes
-
172
#1
01AC
Frequency reference bias low-
er limit (UP/DOWN command
2)
-99.9 to 0.0%
(n011/100%)
0.1%
0.0%
Yes
-
173
01AD
DC Injection Braking Propor-
tional Gain
1 to 999
1 = 0.001
83
(0.083)
No
-
174
01AE
DC Injection Braking Integral
Time Constant
1 to 250
1 = 4 ms
25
(100 ms)
No
-
175
01AF
Reducing Carrier Frequency
Selection at Low Speed
0, 1
-
0
(Note 9)
No
86
176
01B0
Constant Copy Function Se-
lection
rdy, rEd, Cpy,
vFy, vA, Sno
-
rdy
No
138
177
01B1
Constant Read Selection Pro-
hibit
0, 1
-
0
No
139
178
01B2
Fault History
Stores, dis-
plays most
recent 4
alarms
Setting
disabled
-
No
51
179
01B3
Software Version No.
Displays
lower-place 4
digits of soft-
ware No.
Setting
disabled
-
No
-
No. Register
No. for
Trans-
mission
Name
Setting Range Setting Unit
Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page