6. Programming Features
91
* 1. For more information on how to select the sequence polarity, refer to page
192.
* 2. Numbers 1 to 7 are displayed for
to indicate the terminal numbers S1 to
S7.
16
ACCELERATION/
DECELERATION HOLD
command
78
17
LOCAL/REMOTE selection
64
18
Communications/control cir-
cuit terminal selection
94
19
Emergency stop fault,
NO contact input
Inverter stops for an emergen-
cy stop signal input according
to the Stopping Method Selec-
tion (n005). When frequency
coasting to a stop (n005 is set
to 0) is selected, the Inverter
coasts to a stop according to
Deceleration Time Setting 2
(n022).
Digital Operator displays
.
-
20
Emergency stop alarm,
NO contact input
-
21
Emergency stop fault,
NC contact input
-
22
Emergency stop alarm,
NC contact input
-
23
PID control cancel
136
24
PID integral reset
136
25
PID integral hold
136
26
Inverter overheat alert
(OH3 alarm)
When the Inverter overheat
signal turns ON,
(flash-
ing) is displayed at the Digital
Operator.
-
27
Acceleration/deceleration
time selection 2
-
28 to
33
Not used
Set to one of 28 to 33 if a
terminal is not used.
-
34
UP/DOWN commands
Setting enabled only for n056
(terminal S7)
93
35
Self-test
Setting enabled only for n056
(terminal S7)
124
36
UP/DOWN command 2
Setting enabled only for n056
(terminal S7)
-
Setting
Name
Description
Ref.