208
126
017E
Frequency Reference 15
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz
Yes
67
127
017F
Frequency Reference 16
0.00 to 400.0
Hz
0.01 Hz
(less than
100 Hz)/0.1
Hz (100 Hz
or more)
0.00 Hz
Yes
67
128
0180
PID Control Selection
0 to 8
-
0
No
131
129
0181
PID Feedback Gain
0.00 to 10.00
Hz
0.01
1.00
Yes
134
130
0182
Proportional Gain (P)
0.0 to 25.0
0.1
1.0
Yes
133
131
0183
Integral Time (I)
0.0 to 360.0 s
0.1 s
1.0 s
Yes
133
132
0184
Derivative Time (D)
0.00 to 2.50 s
0.01 s
0.00
Yes
133
133
0185
PID Offset Adjustment
−
100% to
100%
1%
0%
Yes
133
134
0186
Upper Limit of Integral Values
0% to 100%
1%
100%
Yes
133
135
0187
Primary Delay Time Constant
for PID Output
0.0 to 10.0 s
0.1 s
0.0 s
Yes
134
136
0188
Selection of PID Feedback
Loss Detection
0 to 2
-
0
No
135
137
0189
PID Feedback Loss Detection
Level
0% to 100%
1%
0%
No
135
138
018A
PID Feedback Loss Detection
Time
0.0 to 25.5 s
0.1 s
1.0 s
No
135
139
018B
Energy-saving Control Selec-
tion (V/f Control Mode)
0, 1
-
0
No
125
140
018C
Energy-saving Coefficient K2
0.0 to 6550
0.1
(Note 7)
No
125
141
018D
Energy-saving Control Voltage
Lower Limit at 60 Hz
0% to 120%
1%
50%
No
126
142
018E
Energy-saving Control Voltage
Lower Limit at 6 Hz
0% to 25%
1%
12%
No
126
143
018F
Power Average Time
1 to 200
1 = 24 ms 1 (24 ms)
No
127
144
0190
Search Operation Voltage
Limit
0% to 100%
1%
0%
No
127
145
0191
Search Operation Voltage
Step at 100%
0.1% to 10.0%
0.1%
0.5%
No
127
No. Register
No. for
Trans-
mission
Name
Setting Range Setting Unit
Factory
Setting
Change
during
Opera-
tion
User
Set-
ting
Ref.
Page