SM input parameter
Index:Sub
Name
Type
Offset
Access Default
Description
0x1C33:00
SM input param-
eter
U8
0
ro
32
0x1C33:01
Synchronization
Type
U16
16
rw
n
0x00: Free Run (not synchronized)
n
0x01: Synchronous with SM3 Event
n
0x02: DC Sync0 – synchronized with Sync0
Event
n
0x03: DC Sync1 – synchronized with Sync1
Event
n
0x22: Synchronous with SM2 Event
0x1C33:02
Cycle time
U32
32
rw
n
Free Run: Time between two local timer
events in ns
n
Free Run: Time between two local timer
events in ns Synchronous SM2 Event: Min-
imum time between two SM2 events in ns
n
DC Sync0: Sync0 Cycle Time (Register
0x9A3-0x9A0) in ns
0x1C33:03
Shift time
U32
64
ro
n
Time between related event and the associ-
ated action (inputs latched from hardware)
n
Shift of Input Latch equal or greater than
0x1C33:09
0x1C33:04
Synchronization
Types supported
U16
96
ro
0x1C33:05
Minimum cycle
time
U32
112
ro
n
Minimum cycle time
supported by the slave
(maximum duration time of the local cycle) in
ns
n
It might be necessary to start the Dynamic
Cycle Time measurement SI04, Bit 14 and
SI08, Bit 0 to get a valid value.
n
Used in Synchronous or DC Mode
0x1C33:06
Calc and Copy
Time
U32
144
ro
Time in ns needed by the application controller to
perform calculations on the input values if neces-
sary and to copy the process data from the local
memory to the Sync Manager before the data is
available for EtherCAT.
0x1C33:07
U32
176
ro
Reserved
0x1C33:08
Get Cycle Time
U16
208
ro
n
Bit 0:
–
0: Measurement of local cycle time
stopped
–
1: Measurement of local cycle time
started
If written again, the measured values are reset
Used in Synchronous or (DC Mode with variable
Cycle Time)
n
Bit 1:
–
0: Reserved
–
1: Reset the error counters
n
Bit 15 … 2: Reserved
0x1C33:09
Delay Time
U32
224
ro
n
Only important for DC Sync1 (Synchroniza-
tion type = 3), if the Input Latch is started by
the Sync1-event
n
Hardware delay time of the slave.
n
Used in DC mode
System SLIO
Deployment
Object Dictionary
HB300 | IM | 053-1EC01 | en | 22-30
91