1
Shield bus carrier
2
Shield bus (10mm x 3mm)
3
Shield clamp
4
Cable shield
To attach the shield the mounting of shield bus carriers are necessary. The shield bus
carrier (available as accessory) serves to carry the shield bus to connect cable shields.
1.
Each System SLIO module has a carrier hole for the shield bus carrier. Push the
shield bus carrier, until they engage into the module. With a flat mounting rail for
adaptation to a flat mounting rail you may remove the spacer of the shield bus car-
rier.
2.
Put your shield bus into the shield bus carrier.
3.
Attach the cables with the accordingly stripped cable screen and fix it by the shield
clamp with the shield bus.
2.5.2 Wiring 8x periphery modules
CAUTION!
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description,
hazardous voltages are not allowed to be connected to the corresponding
terminal module!
n
With wiring the terminal modules, terminals with spring clamp technology are used for
wiring. The spring clamp technology allows quick and easy connection of your signal
and supply lines. In contrast to screw terminal connections this type of connection is
vibration proof.
Shield attachment
Terminal module terminals
System SLIO
Basics and mounting
Wiring > Wiring 8x periphery modules
HB300 | IM | 053-1EC01 | en | 22-30
23