Index:Sub
Name
Type
Offset
Access Default
Description
0x10F3:00
Diagnosis History
U8
0
ro
0xFF
Diagnosis History
0x10F3:01
Maximum Mes-
sages
U8
16
ro
0xFA
Maximum Messages
0x10F3:02
Newest Message
U8
24
ro
0
Newest Message
n
0x10F3:02 Reading
Newest Message
and
save at user program
n
Bit 0 set again: read again 0x10F3:02 and dif-
ference to previously read value is the
number of new entries
n
0x10F3:xx: Read entries accordingly
0x10F3:03
Newest Acknowl-
edged Message
U8
32
rw
0
Newest Acknowledged Message
0x10F3:04
New Message
Available
Bool
40
ro
0
New Message Available
n
Overwrite Mode:
–
0: newest message was read
–
1: newest message was not read
n
Acknowledge Mode:
–
0: no unacknowledged message
–
1: diagnosis messages are available
which can be acknowledged
0x10F3:05
Flags
U16
48
rw
0
Flags
0x10F3:06
Diagnosis mes-
sage
OCTET-
STRIN
G
ro
0
Diagnosis message
...
...
...
...
...
0x10F3:255
Diagnosis mes-
sage
OCTET-
STRIN
G
ro
0
Diagnosis message
‘Explanation of the elements’ page 82
In the
Diagnosis History
, both the diagnostic and process alarms, as information about
status changes as well as EtherCAT-specific error messages are entered chronologically.
Output mapping modules
Index:Sub
Name
Type
Offset
Access Default
Description
0x1600 ...
0x163F:00
RxPDO Map
U8
0
ro/rw
1
Number of
outputs at
this slot
Entry only available at slots with output modules.
0x1600...
0x163F:01
Output mapping
U32
16
ro/rw
1
n
Bit 7...0: length of the mapped objects in bits
n
Bit 15...8: subindex of the mapped object
n
Bit 31...16: index of the mapped object
Example: 0x7000:01, 1 > at slot 0 the first output
has a length of 1 bit.
0x1600...
0x163F:02
Output mapping
U32
ro/rw
1
0x1600...
0x163F: ...
...
‘Explanation of the elements’ page 82
1) rw only at output modules with variable process output image
Diagnosis History
System SLIO
Deployment
Object Dictionary
HB300 | IM | 053-1EC01 | en | 22-30
85
Содержание SLIO
Страница 1: ...IM 053 1EC01 Manual HB300 IM 053 1EC01 en 22 30 System SLIO Interface module EtherCAT IM 053EC...
Страница 114: ...Appendix System SLIO Appendix HB300 IM 053 1EC01 en 22 30 114...
Страница 115: ...Content A History of changes 116 System SLIO Appendix HB300 IM 053 1EC01 en 22 30 115...